Seed Storage Chamber & Gene Bank

(MID AND SHORT-TERM STORAGE UNIT)

Mode No.: MTS-2-901
Make: Saveer
Total area:53’ x 17’11” x 8’ (L x W x H) With two individual Chambers.
Internal Dimensions:53 x 17’11” x 8’ (W x D x H) This unit is divided into 2 areas by partition 60mm puff wall
Chamber A Size:22’ x 17’6” x8’ (L x W x H)
Chamber B Size:22’ x 17’6” x8’ (L x W x H)
Electrical Zone:4.5’ x 17.11” x8’ (L x W x H) qty 2 ( Both Chamber Side)
Temperature and Humidity range in chamber A:10oC ± 1oC and RH 35% ± 5%
Temperature and Humidity range in chamber B:4oC ± 1oC and RH 35% ± 5%
Acclimatization Chamber A:10oC±1oC and RH 35% ± 5% (Cooling & Humidity in 3 steps, it will help to maintain desired temperature inside the chamber)
Acclimatization Chamber B:4oC±1oC and RH 35% ± 5% (Cooling & Humidity in 3 steps, it will help to maintain desired temperature inside the chamber)
Puff Panel Thickness:80mm PUFF minimum 0.5 mm/PPGI sheets on & Finish (All walls & both sides with galvanization to 180 Ceiling).
Insulated Door:Door of dimension 1200 mm x 2000 mm, flush with panels with automatic door closing mechanism and posiseal closure will be part of the door fixtures. The door will match the thickness of panel, with two window
Floor Insulation:Cemented floor, Aluminium floor plate.
Power Supply:415/3/50Hz
Generator Power Back-up:Genset as per required for both chamber
Racks Material:Made of SS, which can take load of seed bottles.
Number of Racks:Complete Rack facility for the whole chambers
Control System:By Intelligent Climate Control System for Temperature and Humidity with recorder and interface to monitor and operate the system through computer.

Refrigeration Piping, Fittings & Valves (Installation Standards General):

The piping will be of refrigeration quality seamless copper tubes and the valves will be bras somatic / standard make. The piping will be include accessories such as filter, drier, sight glass, heat exchanger, sucti online accumulator etc. Adequate number of supports will be included for pipe installation pipe will be insulated with preformed sections of pipe insulation material.

The suction air discharge lines will be designed for a maximum pressure drop corresponding to 1.1oCdrop in saturated evaporating and condensing temperatures.

The liquid line will be designed for maximum pressure drop corresponding to a drop 0.5 to1 oC instauration temperature.

The piping will be designed with proper shape in the direction of Refrigerant flow and proper oil. Return to the compressor and will be installed with adequate supports to avoid undue vibration.

The piping will be thoroughly cleaned as per standard practice prior to installation.

Suction line in solution with 50 mm thick EPS covered with 0.6 mm thick aluminum cladding/25mm thick EPDM insulation/XLPE with proper sealing of joints and factory backed aluminum foil as per standard practice.

Water piping complete with fittings, valves as necessary for supply from a common point near machine room.

Drain piping with rigid PVC pipe from A.C. units to outside the machine rooms complete with 'U' traps and supports.

Controls and Instrument as follows:

Intelligent Climate Control System:

It is a customized climate control system for complete lab which monitors and control temperature Humidity and Light with recording facility.

Miscellaneous Items:

Vibration isolators for condensing units etc.
Minor structural openings in walls/panels etc. for piping, cabling etc. and finishing.

Electrical work for Refrigeration System:

Electrical control panel cubical type, dust and vermin proof copper bus bars and suitable for 400 /440 Volts, 3 phase, 50 C/s A.C. supply and in cooperating the following:

Incoming MCCB 160 A.
Earth leakage current ELR and suitable ELCB.
MCBs and starters for condensing units, air handling unit, ACUs in entire chambers.
MCBs for control circuit
MCBs as spare.
MCBs for capacitors.

The control panel will have provision for inter locking of various equipment as per standard practice.

Power wiring with ISI approved PVC insulated copper conductors with supports, cable trays etc. to be laid on walls/trenches/under the ceiling.

Insulated Panel Structure:

This will cover supply of PUF insulated sandwich panels only with CFC free Polyurethane insulation of 40±2Kg/m3 density with internal metal skin of galvanized steel with plastic coating and external metal skin of galvanized. Steel will duly painted with corrosion resistance paint. The panel will be approx. 1180 mm width and will have required lengths to suit height of the seed storage unit.

The joints will have metal/HIP cam lock or tongue & groove joint arrangement. The scope of work will cover all other ancillary material such as angles, metal sections, flashing, sealant, vapor barrier, adhesive and all other hardware for fixing the panels with the civil structure and pressure balancing ports as per requirement. The ceiling panels will be supported on the panel walls and will have additional support as necessary from the trusses/purlins of the main roof. In case the ceiling panels have joints, it will have supporting member below of the joints. The wall and ceiling insulation thickness will be with 80 mm PUF.

Door Specifications:

Door will be of standard dimension of W 1200 x H 2000 mm and will be fitted on panel opening. Automatic door closing mechanism and positive seal closure will be part of the door fixtures. The door will match with the thickness of the wall panel. The door panel will be hinged to door frame and line panel will rise while opening to prevent bottom gasket from scraping on floor.